Pipe/Equipment Head Insulation & Pipe Weight

Equipment head (cover) insulation volume and area, steel pipe weight, and pipe insulation volume/surface-area with an insulation-layer-thickness lookup.

Name Dia D (mm) Thickness t (mm) Quantity n Volume (m³) Area (m²)
Total volume
Total area
Name Outer dia D (mm) Wall δ (mm) Count Length (m) Weight (kg)
Total weight
t
Spec Outer dia B (mm) Length (m) Insulation t (mm) Insulation volume E (m³) Surface area F (m²)
Total volume
Total area
Pipe outer-diameter lookup (DN → OD)
SpecOuter dia (mm)

Head volume V = ((D/1000 + 1.033·t/1000)²)/4·π·1.033·t/1000·1.5·n; area A = ((D/1000 + 2.1·t/1000)²)/4·π·1.5·n. Pipe weight W = π·(D/1000 − δ/1000)·78.5·δ/1000·100·count·length. Pipe insulation volume E = π·(B/1000 + 1.033·t/1000)·(1.033·t/1000)·length; surface area F = π·(B/1000 + 2·t/1000 + 2·t/1000·0.05 + 0.0032 + 0.005)·length. π = 3.1415926.