UPVC Drainage Pipe Tightness Test Leakage
Allowable leakage = 0.0046·D; measured leakage q = W/(2·T·L); average = q·1440.
mm
m
Allowable leakage
—
m³/(24h·km)
| No. | Start time T1 | End time T2 | Constant pressure time T | Top-up water W | Measured leakage q |
|---|
Average measured leakage
—
m³/(24h·km)
Allowable leakage
—
m³/(24h·km)
Judgement
—
Allowable leakage = 0.0046·D (m³/(24h·km)); q = W/(2·T·L) (L/(min·m)); average = q·1440 (m³/(24h·km)). The section passes when the average measured leakage is not greater than the allowable leakage.