Water-Supply Diameter Selection

Size a water-supply pipe by pressure drop, or pre-size for a pump flow and verify the resulting velocity and pressure drop.

Recommended velocity 1.2–2.0 m/s on mains; pressure drop 0.3–0.5 kgf/cm² (3–5 m head) per segment.
Calculated diameter
mm
Design flow
L/s
Design flow
m³/h
Enter the nominal diameter; if the computed value turns red, increase the diameter, if it turns green the size is acceptable.
Velocity
m/s
Pressure drop
kgf/cm²
Diameter verdict

Size by drop: D = √(72·v·L / Δp) mm; design flow Q = ((D/100)·0.01·D)… = ((D·0.01)/2)²·π·v·10 (L/s), ×3.6 = m³/h. Verify: v = 354·Q/D² (m/s); Δp = 72·v·L/D² (kgf/cm²); green when 0.3–0.5 kgf/cm², otherwise enlarge the diameter.