LV Breaker Selectivity
Check total selectivity between an upstream main breaker and a branch breaker by the instantaneous-trip setting ratio and by the downstream let-through I²t vs the upstream breaking I²t capability.
Inputs
A
A
A
A
kA
ms
kA²s
Results
Note — Selectivity holds when the upstream instantaneous setting clears the branch let-through current with margin and the upstream I²t breaking capability exceeds the downstream let-through I²t. The 1.4× ratio is a typical design margin; confirm against the manufacturer energy-limiting (I²t) curves and a certified engineer. For partial selectivity use only the I²t criterion.