Step 1: Determine flash ratio

SH: Sensible heat of condensate at high pressure before discharge (kJ/kg)

SL: Sensible heat of condensate at low pressure after discharge (kJ/kg)

H: Latent heat of vaporization of steam at low pressure (kJ/kg)

kJ/kg Reference: water sensible heat table
kJ/kg Reference: water sensible heat table
kJ/kg Reference: vaporization latent heat table
kg/h Known condensate mass flow
% (SH - SL) / H x 100
kg/h Condensate x flash ratio

Step 2: Cross-sectional area

Ms: Flash steam mass flow from step 1

kg/h
kg/m³ From steam table
m/s Design velocity
Ms / (3600 x Vs)

Step 3: Tank diameter

m (4 x As / PI)^0.5

Step 4: Height / Diameter = 1.5

m
m
m Height / Diameter = 1.5