Relief Set Pressure (para. 845.4.1)
Maximum pressure that pressure-relieving and pressure-limiting stations must be able to prevent: MAOP + 4% when the hoop stress at MAOP exceeds 72% of SMYS, or the lesser of MAOP + 10% and the pressure producing a hoop stress of 75% of SMYS otherwise.
Inputs
Unit system
psig
in
in